IOCP settings depend on maximum short-circuit current and protection coverage, following IEC 60909 (short-circuit current calculation) and IEC 60255-151 (overcurrent protection settings). (1) Instantaneous Pickup Setting (Iinst) Iinst = Krel × I(3)k. Its defining feature is zero intentional time delay (or minimal delay), with typical operating times of 20–50 ms, complying with IEC 60255-151 (Overcurrent Protection. Ii setting allows normal transient overcurrent inrush current for transformers: A 1st peak 10 to 25 x In Motor direct on line starting current: NOTE: MasterPacT MTZ1 L1 type circuit breakers are equipped with an additional fast instantaneous trip set at 10 x In. These protection devices, namely relays, can respond instantly to serious problems, or allow for short recovery time following minor, routine events. Perhaps the. An Overcurrent Relay Setting Calculator is a online calculator tool that determines the proper relay settings to safeguard electrical circuits against excessive current flow. When relay settings are correct, they isolate faults quickly and prevent damage.